MZ Automation lib60870
View CSAF

Summary

Successful exploitation of these vulnerabilities could crash the device being accessed.

The following versions of MZ Automation lib60870 are affected:

  • lib60870 2.4.0 (CVE-2026-61893, CVE-2026-63033)
CVSS Vendor Equipment Vulnerabilities
v3 6.5 MZ Automation GmbH MZ Automation lib60870 Out-of-bounds Read

Background

  • Critical Infrastructure Sectors: Energy, Water and Wastewater, Critical Manufacturing, Chemical
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: Germany

Vulnerabilities

Expand All +

CVE-2026-61893

A crafted IEC 60870-5-104 I-frame with TypeID 104 (C_TS_NA_1) and an inflated object count causes TestCommand_getFromBuffer to read one byte past the end of the heap-allocated message buffer.

View CVE Details


Affected Products

MZ Automation lib60870
Vendor:
MZ Automation GmbH
Product Version:
MZ Automation GmbH lib60870: 2.4.0
Product Status:
known_affected
Remediations

Mitigation
MZ Automation recommends users update to version 2.4.1 when available.

Vendor fix
See MZ Automation advisories for more information: https://github.com/mz-automation/lib60870/security/advisories/GHSA-g3w7-x5rx-83xm
https://github.com/mz-automation/lib60870/security/advisories/GHSA-g3w7-x5rx-83xm

Relevant CWE: CWE-125 Out-of-bounds Read


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L
4.0 6.9 MEDIUM CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N

CVE-2026-63033

A crafted IEC 60870-5-104 I-frame with a declared object count exceeding what fits in the ASDU body causes InformationObject_ParseObjectAddress to read one byte past the end of the heap-allocated message buffer.

View CVE Details


Affected Products

MZ Automation lib60870
Vendor:
MZ Automation GmbH
Product Version:
MZ Automation GmbH lib60870: 2.4.0
Product Status:
known_affected
Remediations

Mitigation
MZ Automation recommends users update to version 2.4.1 when available.

Vendor fix
See MZ Automation advisory for more information: https://github.com/mz-automation/lib60870/security/advisories/GHSA-7v97-jmwv-w5j7 
https://github.com/mz-automation/lib60870/security/advisories/GHSA-7v97-jmwv-w5j7

Relevant CWE: CWE-125 Out-of-bounds Read


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L
4.0 6.9 MEDIUM CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N

Acknowledgments

  • arun babu puthuparambil of Central Power Research Institute, Bengaluru, India reported these vulnerabilities to CISA

Legal Notice and Terms of Use

This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).


Recommended Practices

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.


Revision History

  • Initial Release Date: 2026-07-30
Date Revision Summary
2026-07-30 1 Initial Publication

Legal Notice and Terms of Use

https://www.cisa.gov/news-events/ics-advisories/icsa-26-211-11