Summary
Successful exploitation of these vulnerabilities could crash the device being accessed.
The following versions of MZ Automation lib60870 are affected:
- lib60870 2.4.0 (CVE-2026-61893, CVE-2026-63033)
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 6.5 | MZ Automation GmbH | MZ Automation lib60870 | Out-of-bounds Read |
Background
- Critical Infrastructure Sectors: Energy, Water and Wastewater, Critical Manufacturing, Chemical
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Germany
Vulnerabilities
CVE-2026-61893
A crafted IEC 60870-5-104 I-frame with TypeID 104 (C_TS_NA_1) and an inflated object count causes TestCommand_getFromBuffer to read one byte past the end of the heap-allocated message buffer.
Affected Products
MZ Automation lib60870
MZ Automation GmbH
MZ Automation GmbH lib60870: 2.4.0
known_affected
Remediations
Mitigation
MZ Automation recommends users update to version 2.4.1 when available.
Vendor fix
See MZ Automation advisories for more information: https://github.com/mz-automation/lib60870/security/advisories/GHSA-g3w7-x5rx-83xm
https://github.com/mz-automation/lib60870/security/advisories/GHSA-g3w7-x5rx-83xm
Relevant CWE: CWE-125 Out-of-bounds Read
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6.5 | MEDIUM | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L |
| 4.0 | 6.9 | MEDIUM | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N |
CVE-2026-63033
A crafted IEC 60870-5-104 I-frame with a declared object count exceeding what fits in the ASDU body causes InformationObject_ParseObjectAddress to read one byte past the end of the heap-allocated message buffer.
Affected Products
MZ Automation lib60870
MZ Automation GmbH
MZ Automation GmbH lib60870: 2.4.0
known_affected
Remediations
Mitigation
MZ Automation recommends users update to version 2.4.1 when available.
Vendor fix
See MZ Automation advisory for more information: https://github.com/mz-automation/lib60870/security/advisories/GHSA-7v97-jmwv-w5j7
https://github.com/mz-automation/lib60870/security/advisories/GHSA-7v97-jmwv-w5j7
Relevant CWE: CWE-125 Out-of-bounds Read
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6.5 | MEDIUM | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:L |
| 4.0 | 6.9 | MEDIUM | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N |
Acknowledgments
- arun babu puthuparambil of Central Power Research Institute, Bengaluru, India reported these vulnerabilities to CISA
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
Revision History
- Initial Release Date: 2026-07-30
| Date | Revision | Summary |
|---|---|---|
| 2026-07-30 | 1 | Initial Publication |