Summary
Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code (CVE-2023-4863), bypass authentication (CVE-2026-16436 and CVE-2026-16437), or perform arbitrary operations (CVE-2026-16438), resulting in information disclosure, tampering with, destruction, or deletion of information, and a denial-of-service (DoS) condition of the system.
The following versions of Mitsubishi Electric GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, IoTWorX, MC Works64, GENESIS32 and BizViz are affected:
- Mitsubishi Electric GENESIS64>=10.97|
- Mitsubishi Electric ICONICS Suite>=10.97|
- Mitsubishi Electric GENESIS
- Mitsubishi Electric GENESIS64
- Mitsubishi Electric ICONICS Suite
- Mitsubishi Electric Hyper Historian
- Mitsubishi Electric AnalytiX
- Mitsubishi Electric MobileHMI
- Mitsubishi Electric IoTWorX
- Mitsubishi Electric MC Works64 vers:all/* (CVE-2026-16436, CVE-2026-16437, CVE-2026-16438)
- Mitsubishi Electric GENESIS32 vers:all/* (CVE-2026-16436, CVE-2026-16437)
- Mitsubishi Electric BizViz vers:all/* (CVE-2026-16436, CVE-2026-16437)
| CVSS | Vendor | Equipment |
|---|---|---|
| v3 9.1 | Mitsubishi Electric | Mitsubishi Electric GENESIS64 |
| 3 Vulnerabilities |
|---|
| Out-of-bounds Write, Weak Password Recovery Mechanism for Forgotten Password, Incorrect Privilege Assignment |
Background
- Critical Infrastructure Sectors: Critical Manufacturing
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: United States
Vulnerabilities
4 Affected Products
Mitsubishi Electric GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64 is included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64 is included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64 is included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64 is included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.97.3 or later for GENESIS64 and ICONICS Suite. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". Note: GENESIS64 is included in the ICONICS Suite installation. For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers using the affected product who cannot immediately update it, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Relevant CWE: CWE-787 Out-of-bounds Write
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.2 | HIGH | CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H |
| 4.0 | 9.3 | CRITICAL | CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H |
23 Affected Products
Mitsubishi Electric GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Relevant CWE: CWE-640 Weak Password Recovery Mechanism for Forgotten Password
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.1 | HIGH | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H |
| 4.0 | 9.2 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
42 Affected Products
Mitsubishi Electric GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 11.04 or later for GENESIS. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend performing the following steps for GENESIS, GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI and MC Works64, to minimize the risk of exploitation of this vulnerability. (1) Delete the .dat file at the location specified below. This file name and location is different depending on the product version. (Version 10: C:Program FilesICONICSGENESIS64ComponentsClientChallengeTable.dat; Version 11: C:ProgramDataICONICS11SecurityChallenges.dat) (2) Create a blank file with the same name and location. (3) Restrict the file system write and delete access to this file to a unique administrator account, different than the GENESIS administrator account.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for IoTWorX. Please download the fixed version from the link below and install it: "https://hub.docker.com/r/iconics/iotworx". For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric Iconics Digital Solutions has no plans to release fixed versions for GENESIS32 or BizViz. For customers using GENESIS32 or BizViz, Mitsubishi Electric Iconics Digital Solutions recommends taking the mitigations described in the Mitsubishi Electric Iconics Digital Solutions' whitepaper which can be found at "https://iconics.com/about/security/cert". Alternatively, customers should consider replacing GENESIS32 or BizViz with GENESIS64 or GENESIS.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Relevant CWE: CWE-640 Weak Password Recovery Mechanism for Forgotten Password
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6.4 | MEDIUM | CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H |
| 4.0 | 7.1 | HIGH | CVSS:4.0/AV:L/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
53 Affected Products
Mitsubishi Electric GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:>=10.97|
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Product Status: known_affected
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions IoTWorX:
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions GENESIS32: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric Iconics Digital Solutions BizViz: vers:all/*
Product Status: known_affected
Remediations
Mitsubishi Electric GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric MC Works64: vers:all/*
Product Status: known_affected
Remediations
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions GENESIS64:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
No fix planned
Mitsubishi Electric has no plans to release a fixed version of MC Works64. For customers using MC Works64, Mitsubishi Electric recommends taking the mitigations described in the Mitsubishi Electric's security advisory at "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-006_en.pdf". Alternatively, customers should consider replacing MC Works64 with GENESIS64 or GENESIS. For information on how to replace it, please refer to the following document: "GENESIS64 ? How to Replace MC Works64 with GENESIS64" (Japanese only): "https://www.mitsubishielectric.co.jp/dl/fa/members/document/manual/scada/bcn-p5999-1459/bcnp59991459a.pdf". Note: This document is published on Mitsubishi Electric FA website, and membership registration and login are required to view it.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions ICONICS Suite:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions Hyper Historian:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions AnalytiX:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Mitsubishi Electric Iconics Digital Solutions MobileHMI:
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Product Status: known_affected
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Product Status: known_affected
Remediations
Vendor fix
Mitsubishi Electric Iconics Digital Solutions is releasing fixed version 10.98 or later for GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, and MobileHMI. Please download the fixed version from the link below and install it: "https://iconicsinc.my.site.com/community/s/resource-center/product-downloads". (Note: GENESIS64, Hyper Historian, AnalytiX, and MobileHMI are included in the ICONICS Suite installation.) For more information on the fixed version, please refer to the Mitsubishi Electric Iconics Digital Solutions whitepaper on security vulnerabilities, which can be found at "https://iconics.com/about/security/cert".
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend configuring the PCs with the affected product installed so that only an administrator can log in, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking remote login from untrusted networks and hosts, and from non-administrator users, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. and allowing remote login only to administrator when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend restricting physical access to the PC with the affected product installed and the network to which the PC is connected, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend preventing the user from clicking on web links in emails from untrusted sources, or from opening attachments in untrusted emails, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend using the PCs with the affected product installed in the LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend blocking unauthorized access by using a firewall, virtual private network (VPN), etc. when internet access is required, to minimize the risk of exploitation of this vulnerability.
Mitigation
For customers of products that do not have a fixed version or who cannot immediately update the product, Mitsubishi Electric and Mitsubishi Electric Iconics Digital Solutions recommend installing anti-virus software on the PC with the affected product installed, as well as on any PCs that can access it, to minimize the risk of exploitation of this vulnerability.
Additional Metrics
Relevant CWE: CWE-266 Incorrect Privilege Assignment
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 9.1 | CRITICAL | CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H |
| 4.0 | 9.4 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H |
Acknowledgments
- Mitsubishi Electric discovered these vulnerabilities.
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Mitsubishi Electric 2026-006 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Mitsubishi Electric directly for any questions regarding this advisory.
Revision History
- Initial Release Date: 2026-10-15
| Date | Revision | Summary |
|---|---|---|